4 Faults and alarms
4.2 List of faults and alarms
4: Instant of the actual value sensing Ti is not an integer multiple of the current controller sampling time.
5: Instant of the setpoint acceptance To >= Bus cycle time Tdp or To = 0.
6: Instant of the setpoint acceptance To is not an integer multiple of the current controller sampling time.
7: Master application cycle time Tmapc is not an integer multiple of the speed controller sampling time.
8: Bus reserve bus cycle time Tdp - data exchange time Tdx less than two current controller sampling times.
10: Instant of the setpoint acceptance To <= data exchange time Tdx + current controller sampling time
11: Master application cycle time Tmapc > 14 x Tdp or Tmapc = 0.
12: PLL tolerance window Tpll_w > Tpll_w_max.
13: Bus cycle time Tdp is not a multiple of all basic clock cycles p0110[x].
16: For COMM BOARD, the instant in time for the actual value sensing Ti is less than two current controller sampling
times.
Remedy:
- Adapt the bus parameterization Tdp, Ti, To.
- adapt the sampling time for the current controller or speed controller.
For alarm value = 10:
- reduce Tdx by using fewer bus participants or shorter telegrams.
Note:
PB: PROFIBUS
PN: PROFINET
F01910 (N, A)
Fieldbus: setpoint timeout
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, ENC, TB30, TM120, TM150, TM31, VECTOR_G
Component:
None
Reaction:
Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The reception of setpoints from the fieldbus interface (onboard, PROFIBUS/PROFINET/USS) has been interrupted.
- bus connection interrupted.
- controller switched off.
- controller set into the STOP state.
See also: p2040 (Fieldbus interface monitoring time), p2047 (PROFIBUS additional monitoring time)
Remedy:
Restore the bus connection and set the controller to RUN.
Note regarding PROFIBUS slave redundancy:
For operation on a Y link, it must be ensured that "DP alarm mode = DPV1" is set in the slave parameterization.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01911 (N, A)
PB/PN: clock cycle synchronous operation clock cycle failure
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF1 (OFF3)
Infeed: OFF1
Acknowledge:
IMMEDIATELY
Cause:
The global control telegram to synchronize the clock cycles has failed - in cyclic operation - for several DP clock
cycles or has violated the time grid specified in the parameterizing telegram over several consecutive DP clock
cycles (refer to the bus cycle time, Tdp and Tpllw).
Remedy:
- check the physical bus configuration (cable, connector, terminating resistor, shielding, etc.).
- check whether communication was briefly or permanently interrupted.
- check the bus and controller for utilization level (e.g. bus cycle time Tdp was set too short).
PB: PROFIBUS
PN: PROFINET
1490
Propagation:
GLOBAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A