F01380
Topology: Actual topology EEPROM defective
Message value:
Preliminary component number: %1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
When detecting the actual topology, a component with a defective EEPROM was detected.
Fault value (r0949, interpret hexadecimal):
bbbbaaaa hex:
bbbb = reserved
aaaa = preliminary component number of the defective components
Remedy:
Output the fault value and remove the defected component.
A01381
Topology: power unit incorrectly inserted
Message value:
Component: %1, to %2, %3, connection: %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
CU_G130_DP, CU_G130_PN, CU_G150_DP, CU_G150_PN, ENC, HUB, TB30, TM120, TM150, TM31,
TM54F_MA, TM54F_SL
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a power unit in the actual topology that has been incorrectly inserted.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
A01381
Topology: Motor Module incorrectly inserted
Message value:
Component: %1, to %2, %3, connection: %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a Motor Module in the actual topology that has been incorrectly inserted with
respect to the target technology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1411