F01511 (A)
BICO: Interconnection with different scalings
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01512
BICO: No scaling available
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF2
Infeed: OFF2 (OFF1)
Acknowledge:
POWER ON
Cause:
An attempt was made to determine a conversion factor for a scaling that does not exist.
Fault value (r0949, interpret decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply scaling or check the transfer value.
F01513 (N, A)
BICO: Interconnection cross DO with different scalings
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than
the BICO input or the normalized units are the same but the reference values are different.
Example 1:
BICO output with voltage normalized unit, BICO input with current normalized unit, BICO output and BICO input lie in
different drive objects. This means that the factor p2002/p2001 is calculated between the BICO output and the BICO
input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
BICO
Propagation:
BICO
Propagation:
BICO
4 Faults and alarms
4.2 List of faults and alarms
1425