F01649
SI P1 (CU): Internal software error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
VECTOR_G
Component:
Control Unit (CU)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal error in the Safety Integrated software on the Control Unit has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- re-commission the "Safety Integrated" function and carry out a POWER ON.
- Upgrade the firmware of the Control Unit to a later version.
- contact Technical Support.
- replace the Control Unit.
Note:
CU: Control Unit
SI: Safety Integrated
F01650
SI P1 (CU): Acceptance test required
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on monitoring channel 1 requires an acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
130: Safety parameters for monitoring channel 2 not available.
Note:
This fault value is always output when Safety Integrated is commissioned for the first time.
1000: Reference and actual checksum on monitoring channel 1 are not identical (booting).
- as a result of the changed current controller sampling time (p0115[0]), the clock cycle time for the Safety Integrated
Basic Functions (r9780) was adapted.
- at least one checksum-checked piece of data is defective.
- safety parameters set offline and loaded into the Control Unit.
2000: Reference and actual checksum on monitoring channel 1 are not identical (commissioning mode).
- reference checksum on monitoring channel 1 incorrectly entered (p9799 not equal to r9798).
- when deactivating the safety functions, p9501 or p9503 were not deleted.
2001: Reference and actual checksum on monitoring channel 2 are not identical (commissioning mode).
- reference checksum on monitoring channel 2 incorrectly entered (p9899 not equal to r9898).
- when deactivating the safety functions, p9501 or p9503 are not deleted.
2002: Enable of safety-related functions between the two monitoring channels differ (p9601 not equal to p9801).
2003: Acceptance test is required as a safety parameter has been changed.
2004: An acceptance test is required because a project with enabled safety-functions has been downloaded.
2005: The Safety logbook has identified that a functional safety checksum has changed. An acceptance test is
required.
2010: Enable of safety-related brake control between the two monitoring channels differ (p9602 not equal to p9802).
2020: Error when saving the safety parameters for the monitoring channel 2.
3003: Acceptance test is required as a hardware-related safety parameter has been changed.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1435