A02098
MTrace 1: cannot be saved
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to save the measurement results of a multiple trace on the memory card (trace recorder 1).
A multiple trace is not started or is canceled.
Alarm value (r2124, interpret decimal):
1: Memory card cannot be accessed.
- card is not inserted or is blocked by a mounted USB drive.
3: data save operation to slow.
- a second trace has been completed before the measurement results of the first trace were able to be saved.
- writing the measurement result files to the card is blocked by the parameter save.
4: Data save operation canceled.
- for instance, the file required for the data save operation was not able to be found.
See also: p4840 (MTrace cycle number setting)
Remedy:
- insert or remove the memory card.
- use a larger memory card.
- configure a longer trace time or use an endless trace.
- avoid saving parameters while a multiple trace is running.
- check whether other functions are presently accessing measurement result files.
A02099
Trace: Insufficient Control Unit memory
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the Control Unit is no longer sufficient for the trace function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace time.
- increase the trace clock cycle.
- reduce the number of signals to be traced.
See also: r4708 (Trace memory space required), r4799 (Trace memory location free)
A02100
Drive: Computing dead time current controller too short
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value in p0118 produces a dead time of one clock cycle because it is prior to setpoint availability.
Possible causes:
- a parameter backup with a version higher than 4.3 was loaded to a version less than or equal to 4.3.
- the system properties after replacing a component no longer match the parameter assignment.
Alarm value (r2134, floating point):
Minimum value for p0118 where dead time no longer occurs.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
BICO
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1509