4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- set p0118 to zero.
- set p0118 to a value greater than or equal to the alarm value (for p1810.11 = 1)
- set p0117 (from the device) to an automatic setting (p0117 = 1).
- check the firmware versions of the components involved.
See also: p0117 (Current controller computing dead time mode), p0118 (Current controller computing dead time)
A02150
TEC: Technology Extension cannot be loaded
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The system was not able to load a Technology Extension.
Alarm value (r2124, interpret hexadecimal):
10 hex (16 dec):
The interface version in the DCB user library is not compatible to the DCC standard library that has been loaded.
12 hex (18 dec):
A technology package was not able to be downloaded to a Control Unit because the warm restart necessary was not
able to be performed.
Only for internal Siemens troubleshooting.
Remedy:
- carry out a warm restart (p0009 = 30, p0976 = 2, 3).
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
For alarm value = 10 hex (16 dec):
Load a compatible DCB user library (compatible to the interface of the DCC standard library).
For alarm value = 12 hex (18 dec):
Carry out a POWER ON (switch-off/switch-on) for all components.
Note:
DCB: Drive Control Block
DCC: Drive Control Chart
TEC: Technology Extension
See also: r4950, r4955, p4956, r4957
F02151 (A)
TEC: internal software error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF2 (NONE, OFF1, OFF3)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software error has occurred within a Technology Extension.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
Note:
TEC: Technology Extension
See also: r4950, r4955, p4956, r4957
Reaction upon A:
NONE
Acknowl. upon A:
NONE
1510
Propagation:
LOCAL
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A