F01946 (A)
PROFIBUS: Connection to the Publisher aborted
Message value:
Fault cause: %1 bin
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
At this drive object, the connection to at least one Publisher for PROFIBUS peer-to-peer data transfer in cyclic
operation has been aborted.
Fault value (r0949, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection aborted.
...
Bit 15 = 1: Publisher with address in r2077[15], connection aborted.
Remedy:
- check the PROFIBUS cables.
- check the state of the Publisher that has the aborted connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01950 (N, A)
PB/PN: clock cycle synchronous operation synchronization unsuccessful
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
OFF1 (NONE)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Synchronization of the internal clock cycle to the global control telegram has failed. The internal clock cycle exhibits
an unexpected shift.
Remedy:
Only for internal Siemens troubleshooting.
Note:
PB: PROFIBUS
PN: PROFINET
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01951
CU SYNC: Synchronization application clock cycle missing
Message value:
%1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
All objects
Component:
None
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
If DRIVE-CLiQ components with different application clock cycle are operated on a DRIVE-CLiQ port, this requires
synchronization with the Control Unit. This synchronization routine was unsuccessful.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the software of the DRIVE-CLiQ components.
- upgrade the Control Unit software.
Note:
If a Controller Extension is being used (e.g. CX32, NX10), then the following applies:
Check whether the Controller Extension is issuing error messages, and if required, remove these.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms