The user agreement is not consistent. After a time of 4 s has expired, the status of the user agreement is different in
both monitoring channels.
1003:
Reference tolerance exceeded.
When the user agreement is set, the difference between the new reference point that has been determined after the
system boots (absolute encoder) or reference point approach (distance-coded or incremental measuring system) and
the safe actual position (saved value + traversing distance) is greater than the reference tolerance (p9544). In this
case, the user agreement is withdrawn.
1004:
Plausibility error for user agreement.
1. If the user agreement has already been set, then the setting is initiated again. In this case, the user agreement is
withdrawn.
2. The user agreement was set, although the axis has still not been referenced.
1005:
- for safe motion monitoring functions without encoder: pulses already suppressed for test stop selection.
- for safe motion monitoring functions with encoder: STO already active for test stop selection.
1011: Acceptance test status between the monitoring channels differ.
1012: Plausibility violation of the actual value from the encoder.
1015: Gearbox switchover (bit 27 in PROFIsafe telegram) takes longer than 2 min.
1020: Cyc. communication failure between the monit. channels.
1021: Cyc. communication failure between the monit. channel and Sensor Module.
1022: Sign-of-life error for DRIVE-CLiQ encoders monitoring channel 1.
1023: Error in the effectiveness test in the DRIVE-CLiQ encoder
1024: Sign-of-life error for HTL/TTL encoders.
1032: Sign-of-life error for DRIVE-CLiQ encoders monitoring channel 2.
1033: Error checking offset between POS1 and POS2 for DRIVE-CLiQ encoder monitoring channel 1.
1034: Error checking offset between POS1 and POS2 for DRIVE-CLiQ encoder monitoring channel 2.
1035: offset between POS1 and POS2 for DRIVE-CLiQ encoder on one of the monitoring channels has changed
since the last commissioning.
1039: Overflow when calculating the position.
1041: Current absolute value too low (encoderless)
1042: Current/voltage plausibility error
1043: Too many acceleration phases
1044: Actual current values plausibility error.
5000 ... 5140:
PROFIsafe message values.
For these message values, the failsafe control signals (failsafe values) are transferred to the safety functions.
5000, 5014, 5023, 5024, 5030 ... 5032, 5042, 5043, 5052, 5053, 5068, 5072, 5073, 5082 ... 5087, 5090, 5091, 5122
... 5125, 5132 ... 5135, 5140:
An internal software error has occurred (only for internal Siemens troubleshooting).
5012: Error when initializing the PROFIsafe driver.
5013: The result of the initialization is different for the two controllers.
5022: Error when evaluating the F parameters. The values of the transferred F parameters do not match the
expected values in the PROFIsafe driver.
5025: The result of the F parameterization is different for the two controllers.
5026: CRC error for the F parameters. The transferred CRC value of the F parameters does not match the value
calculated in the PST.
5065: A communications error was identified when receiving the PROFIsafe telegram.
5066: A time monitoring error (timeout) was identified when receiving the PROFIsafe telegram.
6000 ... 6166:
PROFIsafe message values (PROFIsafe driver for PROFIBUS DP V1/V2 and PROFINET).
For these message values, the failsafe control signals (failsafe values) are transferred to the safety functions. If "Stop
B after failure of the PROFISafe communication" (p9612) is parameterized, the transfer of the failsafe value is
delayed.
The significance of the individual message values is described in safety fault F01611.
7000: Difference of the safe position is greater than the parameterized tolerance (p9542/p9342).
7001: Scaling value for the safe position in the 16 bit notation, too low (p9574/p9374).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1469