Sto Function Via Safety Input Signals; I/O Signal Specifications - Omron R88M-1M Series User Manual

Ac servomotors/servo drives
Hide thumbs Also See for R88M-1M Series:
Table of Contents

Advertisement

8 Safety Function
8-2

STO Function via Safety Input Signals

This section explains how to use the STO function via the safety input signals.
8-2-1

I/O Signal Specifications

The following I/O signals are available to use the STO function: the safety input signals (SF1 and SF2)
and the external device monitoring (EDM) output signal.
Refer to 3-1-5 Control I/O Connector (CN1) Specifications on page 3-27 for I/O signal connection and
external signal processing.
Safety Input Signals
Two safety input circuits are installed to operate the STO function.
Signal
Safety input 1
Safety input 2
• When safety input 1 or 2 turns OFF, the STO function will start operating within 5 ms after the input,
and the motor output torque will be cut off.
• Connect the equipment so that the safety input circuit turns OFF when the STO function is activated.
• Set the operation when the safety input turns OFF in the Stop Selection – Shutdown Option Code
(3B20-01 hex).
Precautions for Correct Use
L pulses for self-diagnosis of safety equipment
When you connect a safety device, such as a safety controller or a safety sensor, the safety
output signal of the device may include L pulses for self-diagnosis. To avoid malfunction due to
the L pulses for self-diagnosis, a filter that removes the L pulses is built into the safety input cir-
cuit. If the OFF time of the safety input signal is 1 ms or less, the safety input circuit does not
recognize it as OFF. To make sure that OFF is recognized, maintain the OFF status of safety
input signal for at least 5 ms.
Safety
Input signal
1 ms or less
Servo Drive
operation
8 - 4
AC Servomotors/Servo Drives 1S-series with Built-in EtherCAT® Communications User's Manual (I586)
Symbol
Pin No.
SF1+
CN1-3,23
The upper arm drive signal of the power transistor inside the
Servo Drive is cut off.
SF1-
CN1-4,24
SF2+
CN1-5,25
The lower arm drive signal of the power transistor inside the
Servo Drive is cut off.
SF2-
CN1-6,26
For self-diagnosis
L pulse
Normal operation
Description
5 ms or more
5 ms or less
STO status

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R88m-1l seriesR88d-1sn ect seriesR88d-1sn01l-ectR88d-1sn02l-ectR88d-1sn04l-ectR88d-1sn01h-ect ... Show all

Table of Contents