SACE Emax 2 DOC. N° 1SDH001316R1002 - ECN000297030 EMAX LOW VOLTAGE AIR CIRCUIT-BREAKERS E1.2-E2.2-E4.2-E6.2 SACE Emax 2 Instructions for using Ekip Touch protection trip units and Acces- sories.
CB if faulty operating conditions occur. In the event of an alarm, it commands a TRIP Ekip Touch Trip unit for SACE Emax 2 CBs, equipped with touchscreen display and available in four different versions Trip coil CB opening actuator controlled directly by Trip unit...
ABB | SACE Emax 2 Introduction 1 - Contents Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Emax 2 CBs, among which: general overview: operating conditions consultation of menus for changing parameters and displaying measurements...
• anyone who is implementing procedures or using maintenance devices recommended by ABB or not must check carefully that neither their personal safety nor the safety devices are endangered by the installation, operation, maintenance method or by the tools used; contact your nearest ABB representative for further information, explanations or specific problems •...
Trip unit Overview 1 - General characteristics Main functions SACE Emax 2 can be configured using the Ekip Touch trip unit, which is available in several versions and able to provide, protection, measurement and signalling functionalities. Emax 2 can be provided with mechanical, electronic and testing accessories, and is supported by many different types of software and applications enabling the functions of the Trip unit and circuit-breaker to be expanded.
To ensure your unit is in secure conditions, the Wizard window immediate asks you to change the PIN code on first power up; this is strongly recommended by ABB. Description The PIN code is a number formed by five digits, each of which can be given a value from 0 to 9; the default value is: 00001 and can be changed in the Settings - New PIN menu.
Direction of current flow Further details about the protections are given in document 1SDH001330R1002. protection cannot be deactivated; its trip parameters are set by ABB and cannot be edited not available with LSI version of Trip unit can be activated with protection MCR = Disable can be activated with protection I = Disable if the presence of sensor S.G.R.
Signal Suggestions Numerical alarm Internal error; contact ABB if this typoe of error occurs (e.g. 30002) Unit on with auxiliary supply, Local Bus parameter enabled but connection to modules not present, incorrect or communication lost (for more than five Local bus seconds);...
Page 34
Continued from the previous page Signal Suggestions Internal error Internal error; contact ABB if this typoe of error occurs Fault with Ekip Com modules: synchronization problem of SNTP SNTP error synchronization reference module Measurement module parameter reading error, contact ABB...
Page 35
NOTE: check error messages on display before consulting the table; if the suggestions given fail to resolve the problem, call the ABB assistance service and provide the report produced by the Ekip Connect software if possible...
Page 37
Press the opening pushbutton and to lock the circuit- pressed activate the lock breaker in the open The lock in open position is defective Contact ABB position Check Trip coil connection and Trip coil is not connected properly messages on display...
Page 40
We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein.