Electronic board of the CB to which the Trip Unit and all the main accessories and electronic actuators connect Ekip Touch Trip unit for SACE Tmax XT7 CB, equipped with touchscreen display and available in six different versions Trip coil...
ABB | SACE Tmax XT Introduction 1 - Contents Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Tmax XT7 CB, among which: general overview: management operations: putting into service, maintenance, troubleshooting operating conditions...
• anyone who is implementing procedures or using maintenance devices recommended by ABB or not must check carefully that neither their personal safety nor the safety devices are endangered by the installation, operation, maintenance method or by the tools used; contact your nearest ABB representative for further information, explanations or specific problems •...
ABB | SACE Tmax XT Trip unit Overview 1 - General characteristics Families SACE Tmax XT7 can be configured to operate with two Trip unit families: • Ekip Dip with interface via dip-switches • Ekip Touch with touchscreen display Both families provide protection and measuring functions related to signals from the installation and are available in different models and versions.
The extensions (additional SW packages) can be pre-engineered when the circuit-breaker is ordered or at a later date (in this case, via ABB Ability Marketplace Ekip Touch Figure 3 Ekip Touch is available in two versions: Ekip Touch LSI and Ekip Touch LSIG.
Ekip Supply Power supply of Trip unit and modules in terminal box Ekip Com Communication between Trip unit and external buses (various protocols) Communication between Trip units via an intranet with ABB proprietary Ekip Link protocol Ekip Signalling 2K Programmable digital inputs/outputs...
Page 16
• UniSec, for configuring medium voltage switchgear Front CAD Software comprising libraries of block graphics for ABB panel-making products to be used with the latest versions of AutoCAD, AutoCAD LT, IntelliCAD NOTE: the link launches the software package download, which requires about 190 Mb of space.
Reset Wizard command: in this case, Wizard will appear when the apparatus is powered up the next time. NOTE: for security reasons, ABB strongly advises you to change the PIN right from the first access and to keep it in a safe place...
By activating and using Predictive Maintenance in ABB Ability (EDCS) on the specific switch, you can suggest a different maintenance frequency. Alarms displayed and A list of faults that may appear on the Ekip Touch display is given below along with suggestions on how to...
Page 22
IEEE1588 synch Synchronization problem of IEEE 1588 synchronization reference module MAC Address Ekip Com module detected with incorrect / not allowed MAC address, contact ABB. Ekip Installation Installation error between HMI and Mainboard, contact ABB Measuring Install Measurement module (Settings-Circuit breaker-Installation-Measuring-Install)
Page 23
NOTE: check error messages on display before consulting the table; if the suggestions given fail to resolve the problem, call the ABB assistance service and provide the report produced by the Ekip Connect software if possible...
Disabling The PIN code can be disabled by entering its value as: 00000; In this case, the PIN is only required to change the PIN itself in the Settings menu. Recovery if the PIN code is lost, consult document 1SDH001501r1002, available in the ABB website, or contact ABB directly.
• the device nearest to the fault trips • the other devices are blocked for a programmable time NOTE: connection can be made between ABB devices that have the zone selectivity function Characteristics Ekip Touch has five selectivity connections, located on the rear connectors of the CB:...
Page 78
• The other devices are blocked for a programmable time NOTES: • connection can be made between ABB devices that have the zone selectivity function • disable the zone selectivities of protections S, S2, I, 2I, MCR, G, Gext and MDGF to correctly...
Bluetooth Low Energy connection between the Trip unit and its device is guaranteed thanks to the ABB EPiC application and the pairing configuration described in the next paragraph. WARNING! It is the customer's sole responsibility to provide and continuously ensure a secure connection between his device and the Trip unit.
Replacement The module can be replaced by the user; any Rating Plug with maximum rated current equal to the nominal size of the CB (Iu) can be installed. Further details about assembly and the Rating Plug installation procedure are available in ABB Library, particularly in document 1SDH002011A1505.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
Page 156
Description Identifier and SW version of the module SN and version Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device Remote information Certain additional information concerning the version and status of the module is available via the service connector (via Ekip Connect) or by communication via system bus;...
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
Page 159
IP address of the node to which the module is connected, in the presence of several Gateway address subnets Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device...
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
Page 162
IP address of the node to which the module is connected, in the presence of Gateway address several subnets Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device...
Each Ekip Link can interface with up to 15 actors, of which up to 12 for the Zone Selectivity function. The ports used by the module are: Port Service Notes 18/udp ABB proprietary In the case of rapid exchanges of information among ABB devices 319/udp IEEE 1588 Valid with IEEE 1588 protocol enabled 320/udp 68/udp DHCP client...
Page 166
IP address of the node to which the module is connected, in the presence of Gateway address several subnets Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device...
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or information.
Page 170
IP address of the node to which the module is connected, in the presence of several Gateway address subnets Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to MAC address ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device...
Ekip Supply module on the basis of the customer's own application and network. For applications in low voltage installations ABB suggests use of the external probe PT1000 3mt, is equippped with a nut and screw for use on busbars and is compatible with the dielectric withstand and insulation levels established by standard IEC 60947- 2 (Ui= 1000 V, Uimp= 12 kV).
The inputs and outputs can be fully configured by the user The module can be supplied by 110...240 V AC / DC or 24...48 V DC. Further details about Ekip Signalling Modbus TCP are available in ABB Library, especially in document 1SDH001456r0002.
IMPORTANT: the toroid can be choosen as an alternative to the S.G.R. one: protections Gext, MDGF and Rc are alternatives to each other Further details about the Rc toroid connection are available in ABB Library, especially in document 1SDH001000r0521. 5 - S.G.R. Toroid S.G.R.
Further details about the External neutral connection are available in ABB Library, especially in document 1SDH001000r0506. 7 - Ekip Com Actuator Ekip Com Actuator is an accessory module which allows SACE Tmax XT7 circuit-breakers to be opened and closed remotely. The module is installed on the front of the circuit-breaker, in the accessories area.
• if green, proceed with the required reading and configuring operations • if red, replace the batteries of the device (three 1.5 V AA batteries) Further details are available in ABB Library, especially in document 1SDH001000r0519 Ekip Programming and Ekip Ekip Programming is a supply and communication accessory that is useful for: T&P...