6-6
Status Diagnostic Messages
A0011 Starting lockout active
A0012 Control and power sections ready for operation
For HMS, HMD, HCS
For HMV
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
As an option, certain digital drive controllers can be equipped with a drive
interlock. The drive interlock prevents the unintended start of a servo axis.
This is realized by separating the electronic control system of the power
output stage from the power output stage by means of a relay contact.
When the drive interlock is active the control panel of the drive reads
"AS".
See also Project Planning Manual Control Section, keyword "Drive
interlock"
A0011 - Attributes
Display:
AS
Mess. no.:
A0011 (hex)
Supported by Firmware Variant:
Supported by Supply Unit:
The A0012 Control and power sections ready for operation diagnostic
message signals that the drive is provided with control voltage and the
power has been switched on. The drive is ready for power output.
Note:
This status is displayed on the control panel of the drive with
"Ab" ("Antrieb bereit" = Drive ready).
The diagnostic message A0012 Control and power sections ready for
operation signals that the supply unit is ready for switching in the mains
contactor.
Note:
This status is displayed on the control panel of the device with
"Bb" ("betriebsbereit" = ready for operation).
A0012 - Attributes
Display:
Ab
Mess. no.:
A0012 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.
This answer is automatically generated