7-12
Error Messages

F8016 Automatic commutation: iteration without result

Cause
Current generated during automatic commutation
offset determination could not produce any
saturation effect in motor.
Required maximum current is approx. 1.5-fold
continuous current at standstill (S-0-0111, Motor
current at standstill).
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
During the automatic commutation offset determination (after drive
enable) it has been impossible to find appropriate values for P-0-0506,
Voltage amplitude for angle acquisition and P-0-0507, Test frequency
for angle acquisition with which it would be possible to determine a
useful commutation offset of the connected motor.
Remedy
Check whether controller can supply motor with
sufficiently high current (cf. S-0-0111, Motor current at
standstill and S-0-0110, Amplifier peak current). If
maximum controller current is too low, drive controller
has to be replaced by a bigger one
- or -
Change position of movable part of motor with regard to
its rigid part restart command P-0-0524, C1200
Commutation offset setting command
- or -
Contact our service department and, if necessary, use
an absolute measuring system, because motor
characteristics do not allow automatic commutation
See also Functional Description "Commutation Setting"
F8016 - Attributes
Display:
F8016
Mess. no.:
F8016 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?

Questions and answers

Kaushal patel
January 25, 2025

Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do

1 comments:
Mr. Anderson
February 10, 2025

Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:

1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.

Repeat these steps for all five machines to ensure proper operation.

This answer is automatically generated

Ashok Kumar sharma
March 3, 2025

What is solution of 2110 fault in rexroth drive

1 comments:
Mr. Anderson
March 3, 2025

The solution for the F2110 fault in Bosch Rexroth IndraDrive is:

1. If the failure occurs sporadically (firmware error), clear the error and contact the service department for a firmware update.
2. If the error occurs repeatedly, it indicates defective hardware. In this case, the control section or the entire device must be replaced.
3. Only Rexroth service engineers or specially trained users are allowed to replace the control section.
4. The procedure for replacing the entire drive controller is described in the Project Planning Manual for the power section.

This answer is automatically generated

Aleksandır
March 12, 2025

The engine moves in manual mode but does not work in automatic mode. The error code is E2074. What should I do?

2 comments:
Mr. Anderson
March 12, 2025

Error code F2074 indicates a defective motor encoder. To resolve this issue:

1. Check the position data reference – If the position data reference is incorrect, the encoder is defective.
2. Replace the motor or motor encoder – A faulty encoder can prevent movement in automatic mode.
3. Send the motor to the manufacturer’s service department for inspection.

If the issue persists, consult the service department for further assistance.

This answer is automatically generated

Stephen
March 21, 2025

@Aleksand C0209incorrect encoder configuration error on drive controller display, red light fickering on drive comms port,

Mr.zuma
March 19, 2025

Please help me with the problem of the VM F2802 and E2810 errors on the Rexroth Indradrive M

User image 67da6c3815881
1 comments:
Mr. Anderson
March 19, 2025

The VM F2802 error on the Bosch Rexroth IndraDrive M indicates that the Phase-Locked Loop (PLL) is not synchronized.

The E2810 error means that the drive system is not ready for operation. This occurs when one or more drives in a system (connected via DC bus and module bus) signal an error, preventing the supply from being ready for power output. To resolve it, identify the drives signaling an error and remove the cause, or ensure all drives are in communication phase 4.

This answer is automatically generated

Saleh
March 27, 2025

Medodyjsjddidi

User image 67e59d0957d0e

Subscribe to Our Youtube Channel

Table of Contents

Save PDF