Rexroth IndraDrive
C3001 Synchronization and storage failed
Cause
Another safety technology command is still active,
e.g. C07_2 Load defaults procedure command (load
defaults procedure for safety technology) or safety
technology password writing
Hardware defect of optional module "safety
technology I/O"
C3101 Act. modulo value cycle greater than max. travel range
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
The command P-0-3204, C3000 Synchronize and store safety
technology IDN command was not or incorrectly executed.
Remedy
Wait until active command has been completed and
restart command P-0-3204, C3000 Synchronize and
store safety technology IDN command
Reset optional module "safety technology I/O" by a
restart. If command error occurs repeatedly, hardware
has to be replaced
C3001 - Attributes
Display:
C3001
Mess. no.:
C3001 (hex)
Supported by Firmware Variant:
The command error C3101 is generated when the calculated modulo
value for the actual value cycle is greater than the maximum travel range
(S-0-0278, Maximum travel range).
C3101 - Attributes
Display:
C3101
Mess. no.:
C3101 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
9-111
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.