7-24
Error Messages
F8133 Error when checking interrupting circuits
Cause
An error was detected during check of interrupting
circuit
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
In order to lock the output stage in a safety related way when the safety
technology has detected an error, the correct functioning of the
interrupting circuit is cyclically checked. This is done on the one hand
during the actions "release output stage" and "lock output stage", on the
other hand statically while the output stage is being released or locked.
The corresponding hardware realization ensures that this is possible
without repercussion on the PWM control signals.
The drive torque is immediately disabled. The drive automatically
switches to "safety related standstill" and the output stage is switched off
via one channel. All poles of the mains contactor are switched off.
Note:
Safety is not acknowledged; i.e. "safety technology status
output controller" was cleared/reset in P-0-3214, Safety
technology signal status word, channel 1 or the diagnosis
input/output I/O10n (channel 2) was set depending on the
parameterization in P-0-3210, Safety technology control
word.
Remedy
Error cannot be cleared. Switch power supply off and on
again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F8133 - Attributes
Display:
F8133
Mess. no.:
F8133 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.
This answer is automatically generated
What is solution of 2110 fault in rexroth drive
The solution for the F2110 fault in Bosch Rexroth IndraDrive is:
1. If the failure occurs sporadically (firmware error), clear the error and contact the service department for a firmware update.
2. If the error occurs repeatedly, it indicates defective hardware. In this case, the control section or the entire device must be replaced.
3. Only Rexroth service engineers or specially trained users are allowed to replace the control section.
4. The procedure for replacing the entire drive controller is described in the Project Planning Manual for the power section.
This answer is automatically generated
The engine moves in manual mode but does not work in automatic mode. The error code is E2074. What should I do?
Error code F2074 indicates a defective motor encoder. To resolve this issue:
1. Check the position data reference – If the position data reference is incorrect, the encoder is defective.
2. Replace the motor or motor encoder – A faulty encoder can prevent movement in automatic mode.
3. Send the motor to the manufacturer’s service department for inspection.
If the issue persists, consult the service department for further assistance.
This answer is automatically generated
@Aleksand C0209incorrect encoder configuration error on drive controller display, red light fickering on drive comms port,
Please help me with the problem of the VM F2802 and E2810 errors on the Rexroth Indradrive M
The VM F2802 error on the Bosch Rexroth IndraDrive M indicates that the Phase-Locked Loop (PLL) is not synchronized.
The E2810 error means that the drive system is not ready for operation. This occurs when one or more drives in a system (connected via DC bus and module bus) signal an error, preventing the supply from being ready for power output. To resolve it, identify the drives signaling an error and remove the cause, or ensure all drives are in communication phase 4.