9-4
Command Diagnostic Messages
C07_0 Load defaults procedure com. (load controller param.)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
The C07_0 message on the display of the drive controller shows that the
C07_0
Load
defaults
parameters) command was activated.
The command can be started as follows:
• by means of the S-0-0262, C07_x Load defaults procedure
command parameter or
• by means of the control panel of the drive controller or
• by starting the S-0-0099, C0500 Reset class 1 diagnostics command
if the drive controller displays "RL" (occurs if the S-0-0141, Motor type
and P-0-2141, Motor type, encoder memory parameters are
different).
Note:
With parameter S-0-0262 it is possible to start another
command, the C07_1 Load defaults procedure command
(load base parameters) command. In parameter P-0-4090,
Index for C07 Load defaults procedure it is possible to set
which of both commands is started.
The C07_0 Load defaults procedure command (load controller
parameters) can only be carried out in the case of motors of the MHD,
MKD and MKE series. In the case of these motors, the controller
parameters are loaded from the motor encoder data memory to the drive
controller and some controller parameters are set to their default values.
With the C07_0 Load defaults procedure
command (load controller parameters)
command user-defined controller settings are
overwritten!
CAUTION
⇒ Only use this command if you want to load standard
controller parameter values. For saving and then
loading user-defined parameter values specific
commands are available.
See
also
Functional
Parameters"
See also Functional Description "Control Panel of the IndraDrive
Controllers"
C0700 - Attributes
Display:
C07_0
Mess. no.:
C0700 (hex)
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
procedure
command
Description
"Loading,
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Rexroth IndraDrive
(load
controller
Storing
and
Saving
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.
This answer is automatically generated
What is solution of 2110 fault in rexroth drive
The solution for the F2110 fault in Bosch Rexroth IndraDrive is:
1. If the failure occurs sporadically (firmware error), clear the error and contact the service department for a firmware update.
2. If the error occurs repeatedly, it indicates defective hardware. In this case, the control section or the entire device must be replaced.
3. Only Rexroth service engineers or specially trained users are allowed to replace the control section.
4. The procedure for replacing the entire drive controller is described in the Project Planning Manual for the power section.
This answer is automatically generated
The engine moves in manual mode but does not work in automatic mode. The error code is E2074. What should I do?
Error code F2074 indicates a defective motor encoder. To resolve this issue:
1. Check the position data reference – If the position data reference is incorrect, the encoder is defective.
2. Replace the motor or motor encoder – A faulty encoder can prevent movement in automatic mode.
3. Send the motor to the manufacturer’s service department for inspection.
If the issue persists, consult the service department for further assistance.
This answer is automatically generated
@Aleksand C0209incorrect encoder configuration error on drive controller display, red light fickering on drive comms port,
Please help me with the problem of the VM F2802 and E2810 errors on the Rexroth Indradrive M
The VM F2802 error on the Bosch Rexroth IndraDrive M indicates that the Phase-Locked Loop (PLL) is not synchronized.
The E2810 error means that the drive system is not ready for operation. This occurs when one or more drives in a system (connected via DC bus and module bus) signal an error, preventing the supply from being ready for power output. To resolve it, identify the drives signaling an error and remove the cause, or ensure all drives are in communication phase 4.
This answer is automatically generated