C2103 Brake torque too low

DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
When executing the "brake check" command (C2100) the holding torque
of the brake was detected to be too low.
The command C2100 is aborted if the "abrasion" of the brake was
deactivated via bit 4 in P-0-0525, Holding brake control word.
Otherwise the drive tries to reestablish the brake torque by automatically
starting the abrasion cleaning process and then checks the holding torque
again.
Cause:
Due to storage brake is covered with an oxide layer.
- or -
Brake is wetted with oil or grease.
- or -
Brake is worn.
Remedy:
Start "Brake check" command again in order to reestablish full brake
torque by repeated abrasion.
If brake torque is still too low after several attempts to reestablish it, brake
or motor must be replaced.
See also Functional Description "Motor Holding Brake"
C2103 - Attributes
Display:
C2103
Mess. no.:
C2103 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
9-99

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?

Questions and answers

Kaushal patel
January 25, 2025

Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do

1 comments:
Mr. Anderson
February 10, 2025

Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:

1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.

Repeat these steps for all five machines to ensure proper operation.

This answer is automatically generated

Ashok Kumar sharma
March 3, 2025

What is solution of 2110 fault in rexroth drive

1 comments:
Mr. Anderson
March 3, 2025

The solution for the F2110 fault in Bosch Rexroth IndraDrive is:

1. If the failure occurs sporadically (firmware error), clear the error and contact the service department for a firmware update.
2. If the error occurs repeatedly, it indicates defective hardware. In this case, the control section or the entire device must be replaced.
3. Only Rexroth service engineers or specially trained users are allowed to replace the control section.
4. The procedure for replacing the entire drive controller is described in the Project Planning Manual for the power section.

This answer is automatically generated

Aleksandır
March 12, 2025

The engine moves in manual mode but does not work in automatic mode. The error code is E2074. What should I do?

2 comments:
Mr. Anderson
March 12, 2025

Error code F2074 indicates a defective motor encoder. To resolve this issue:

1. Check the position data reference – If the position data reference is incorrect, the encoder is defective.
2. Replace the motor or motor encoder – A faulty encoder can prevent movement in automatic mode.
3. Send the motor to the manufacturer’s service department for inspection.

If the issue persists, consult the service department for further assistance.

This answer is automatically generated

Stephen
March 21, 2025

@Aleksand C0209incorrect encoder configuration error on drive controller display, red light fickering on drive comms port,

Mr.zuma
March 19, 2025

Please help me with the problem of the VM F2802 and E2810 errors on the Rexroth Indradrive M

User image 67da6c3815881
1 comments:
Mr. Anderson
March 19, 2025

The VM F2802 error on the Bosch Rexroth IndraDrive M indicates that the Phase-Locked Loop (PLL) is not synchronized.

The E2810 error means that the drive system is not ready for operation. This occurs when one or more drives in a system (connected via DC bus and module bus) signal an error, preventing the supply from being ready for power output. To resolve it, identify the drives signaling an error and remove the cause, or ensure all drives are in communication phase 4.

This answer is automatically generated

Saleh
March 27, 2025

Medodyjsjddidi

User image 67e59d0957d0e

Table of Contents

Save PDF