7-28
Error Messages

F8838 Overcurrent external braking resistor

Cause
Resistance value of connected braking resistor is too
low
Short circuit at braking resistor connection
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
The error F8838 is generated when the current in the braking resistor
circuit is rising in an inadmissible way.
Remedy
Connect braking resistor unit with higher resistance
value (take specification into account!)
Remove short circuit
See also Functional Description "Power Supply"
F8838 - Attributes
Display:
F8838
Mess. no.:
F8838 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?

Questions and answers

Kaushal patel
January 25, 2025

Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do

1 comments:
Mr. Anderson
February 10, 2025

Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:

1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.

Repeat these steps for all five machines to ensure proper operation.

This answer is automatically generated

Table of Contents

Save PDF