7-48
Error Messages
F6044 Negative travel range limit switch activated
Cause
Travel range limit switch situated in negative
direction (see Project Planning Manual for motor)
was activated because axis is outside of travel range
that was defined by means of travel range limit
switches
Incorrect parameterization of digital inputs and
outputs on control section
Travel range limit switch or cable is defective or
incorrectly wired
Control section or digital inputs on control section
defective
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
The drive provides a function for monitoring travel range limit switches
(external hardware limit switches).
Note:
This monitor has to be activated and parameterized via
P-0-0090, Travel range limit parameter.
When the error F6044 occurs, the axis is shut down with
velocity command value reset.
Remedy
1. Clear error (reset button or error clearing command)
and switch power on
2. Set drive enable and preset command value that
leads back to the allowed travel range
Correct configuration of digital inputs/outputs and
correct it, if necessary
Check function and wiring of travel range limit switch
Replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
See also Functional Descriptions:
• "Position Limitation/Travel Range Limit Switch"
• "Digital Inputs/Outputs"
F6044 - Attributes
Display:
F6044
Mess. no.:
F6044 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.