9-20
Command Diagnostic Messages
C0105 Maximum length for MDT exceeded
Cause
In S-0-0015, Telegram type parameter telegram
type 7 (configured telegram) was set
Length of configured data record in MDT that is
determined by S-0-0024, Config. list of the master
data telegram exceeds the maximum allowed value
entered in S-0-0186, Length of the configurable
data record in the MDT
C0106 Config. IDNs for AT not configurable
Cause
in the S-0-0015, Telegram type parameter the
telegram type 7 (configured telegram) was set
in S-0-0016, Custom amplifier telegram
configuration list there were some parameters
entered that are not contained in S-0-0187, List of
configurable data in the AT
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command S-0-0127, C0100 Communication
phase 3 transition check an error with regard to the telegram
configuration of the master communication was detected.
Remedy
Set priority telegram (telegram type = 0..6) in S-0-0015,
Telegram type parameter
Reduce number of configured parameters in MDT
(S-0-0024, Config. list of the master data telegram)
Note:
List parameters are only allowed in the multiplex channel.
For removing command errors see "Command Errors"
C0105 - Attributes
Display:
C0105
Mess. no.:
C0105 (hex)
Supported by Firmware Variant:
During
the
transition
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Remedy
set priority telegram (telegram type = 0..6) in S-0-0015,
Telegram type parameter
in S-0-0016, Custom amplifier telegram configuration
list those parameters have to be entered that are
contained in S-0-0187, List of configurable data in the
AT
Note:
List parameters are only allowed in the multiplex channel.
C0106 - Attributes
Display:
C0106
Mess. no.:
C0106 (hex)
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
check
from
communication
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Rexroth IndraDrive
phase 2
to
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers
Our machine in Rexroth drive installation total 20 nos machine so facing issue shortly 5 drive folty 8060 erro so how to do
Error 8060 on Bosch Rexroth IndraDrive indicates an overcurrent in the power section. To resolve this issue for five machines, follow these steps for each machine:
1. Check the Load and Connections – Verify that the motor and power connections are correct and not causing excessive current draw.
2. Inspect the Power Section – Look for any visible damage or overheating signs in the power section.
3. Restart the System – Power off the drive, wait for the DC bus to discharge below 50V, and restart.
4. Adjust Parameters if Needed – Ensure that the drive’s current limits and motor settings are correctly configured.
5. Replace Faulty Components – If the issue persists, the power section may be defective and require replacement.
Repeat these steps for all five machines to ensure proper operation.
This answer is automatically generated
What is solution of 2110 fault in rexroth drive
The solution for the F2110 fault in Bosch Rexroth IndraDrive is:
1. If the failure occurs sporadically (firmware error), clear the error and contact the service department for a firmware update.
2. If the error occurs repeatedly, it indicates defective hardware. In this case, the control section or the entire device must be replaced.
3. Only Rexroth service engineers or specially trained users are allowed to replace the control section.
4. The procedure for replacing the entire drive controller is described in the Project Planning Manual for the power section.
This answer is automatically generated
The engine moves in manual mode but does not work in automatic mode. The error code is E2074. What should I do?
Error code F2074 indicates a defective motor encoder. To resolve this issue:
1. Check the position data reference – If the position data reference is incorrect, the encoder is defective.
2. Replace the motor or motor encoder – A faulty encoder can prevent movement in automatic mode.
3. Send the motor to the manufacturer’s service department for inspection.
If the issue persists, consult the service department for further assistance.
This answer is automatically generated
@Aleksand C0209incorrect encoder configuration error on drive controller display, red light fickering on drive comms port,
Please help me with the problem of the VM F2802 and E2810 errors on the Rexroth Indradrive M
The VM F2802 error on the Bosch Rexroth IndraDrive M indicates that the Phase-Locked Loop (PLL) is not synchronized.
The E2810 error means that the drive system is not ready for operation. This occurs when one or more drives in a system (connected via DC bus and module bus) signal an error, preventing the supply from being ready for power output. To resolve it, identify the drives signaling an error and remove the cause, or ensure all drives are in communication phase 4.
This answer is automatically generated