C0604 Homing of absolute encoder not possible

LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command for drive-controlled homing (C0600)
an error was detected.
Cause:
By the encoder selection in S-0-0147, Homing parameter an absolute
measuring system was selected. The command for drive-controlled
homing can only be executed if the P-0-0012, C0300 Command Set
absolute measuring command had been activated before.
Remedy:
First activate the P-0-0012, C0300 Command Set absolute measuring
command and then start the S-0-0148, C0600 Drive-controlled homing
procedure command. Doing this the absolute reference point is
established.