F2086 Error supply module

Cause
Failure in power supply or overload of power supply
Fatal error message of one or several drives of a
drive system and message signaled to supply
(configuration P-0-0118)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
This error is signaled by the supply to the drives via the module bus. It
has high priority and...
• causes error reaction in the drives in operation. The error message is
displayed at these drives.
• causes power of the supply unit to be switched off or the Bb contact of
converters to open (requires assignment of respective bit P-0-0861,
Status word of power section to digital output!) and possibly causes
DC bus short circuit (requires corresponding wiring!).
This error can also have been caused by a fatal drive error that was
signaled to the supply via the module bus. The respective settings must
be made in P-0-0118, Power supply, configuration.
Remedy
Check power supply
Identify drive or drives signaling a fatal error. Remove
cause of error at respective drive or drives
See also Functional Description "Power Supply"