9-100
Command Diagnostic Messages
C2104 Command execution not possible
Cause
in the P-0-0525, Holding brake control word
parameter the brake has not been activated
the value in P-0-0540, Torque of motor brake is 0
C2202 Error when writing data to non-volatile memory
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
It was impossible to start the "Brake check" command (C2100).
Remedy
activate the brake in the P-0-0525, Holding brake
control word parameter
enter the correct value for P-0-0540, Torque of motor
brake
See also Functional Description "Motor Holding Brake"
C2104 - Attributes
Display:
C2104
Mess. no.:
C2104 (hex)
Supported by Firmware Variant:
During the execution of the S-0-0264, C2200 Backup working memory
procedure command an error occurred.
Cause:
It was impossible to address the active, non-volatile memory (internal
flash memory or MMC, if plugged in) without error.
Remedy:
• First start the command S-0-0264, C2200 Backup working memory
procedure command again. If the error occurs again, then
• replace MMC (if plugged in) if necessary, then start the command
again. If the error occurs again,
• contact the service department.
C2202 - Attributes
Display:
C2202
Mess. no.:
C2202 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Need help?
Do you have a question about the Rexroth IndraDrive and is the answer not in the manual?
Questions and answers