E8028 Overcurrent in power section

Cause
Current loop incorrectly parameterized
In the case of Bosch Rexroth motors with encoder
data memory (MHD, MKD, MKE), values for current
loop parameterization do not correspond to values in
encoder data memory
In the case of Rexroth motors without encoder data
memory, values for current loop parameterization do
not correspond to manufacturer-side specifications
In the case of third-party motors, output data for
calculating parameter values are not correct
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
The controller monitors the motor current (= controller output current)
supplied by the power section.
• If the controller output current is higher than the 1.2-fold of S-0-0110,
Amplifier peak current
- or -
• if the controller output current is higher than the product of P-0-4013,
Current limit value of demagnetization and S-0-0109, Motor peak
current,
the output stage of the power section is locked until the controller output
current has fallen to allowed values again; during this time the warning
E8028 is output.
Remedy
Check current loop setting (S-0-0106, Current loop
proportional gain 1, S-0-0107, Current loop integral
action time 1) and, if necessary, correct it after having
contacted our service department
Check whether values in S-0-0106, Current loop
proportional gain 1 and S-0-0107, Current loop
integral action time 1 correspond to values in encoder
data memory (P-0-2106, Current loop proportional
gain 1, encoder memory and P-0-2107, Current loop
integral-action time 1, encoder memory)
Attention: Calculation of S-0-0106, Current loop
proportional gain 1 depends on P-0-0001, Switching
frequency of the power output stage and P-0-0556,
Control word of axis controller!
Check whether values in S-0-0106, Current loop
proportional gain 1 and S-0-0107, Current loop
integral action time 1 correspond to manufacturer-side
specifications (see DriveTop)
Check whether output data for calculating parameter
values are correct