Debounce times for standard and safety functions
The debounce time p0724 for "standard" digital inputs has no influence on the fail-safe input
signals. Conversely, the same applies: The F-DI debounce time does not affect the signals
of the "standard" inputs.
If you use an input as a standard input, set the debounce time using parameter p0724 .
If you use an input as a fail-safe input, set the debounce time as described above.
6.8.3.7

Setting the forced checking procedure (test stop)

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER and Startdrive
To set the forced checking procedure (test stop) of the basic functions, proceed as follows:
1. Select the screen form for setting the forced checking procedure.
Figure 6-60
Figure 6-61
2. Set the monitoring time to a value to match your application.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Description
F-DI changeover tolerance time (factory setting: 500 ms)
Tolerance time to change over the fail-safe digital input for the basic functions.
STO debounce time (factory setting: 1 ms)
Debounce time of the fail-safe digital input for the basic functions.
Setting the forced checking procedure with STARTER
Setting the forced checking procedure with Startdrive
Advanced commissioning
6.8 Safe Torque Off (STO) safety function
247