Kinetic Buffering (Vdc Min Control) - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.7 Application-specific functions
6.7.6

Kinetic buffering (Vdc min control)

Kinetic buffering increases the drive availability. The kinetic buffering utilizes the kinetic
energy of the load to buffer line dips and failures. During a line dip, the inverter keeps the
motor in the switched-on state for as long as possible. One second is a typical, maximum
buffer time.
Preconditions
The following prerequisites must be fulfilled to practically use the "kinetic buffering" function:
● The driven load has a sufficiently high inertia.
● The application allows a motor to be braked during a power failure.
Function
When the line supply dips or is interrupted, the DC link voltage in the inverter decreases. At
an adjustable threshold, kinetic buffering intervenes (V
forces the load to go into slightly regenerative operation. As a consequence, the inverter
covers its power loss and the losses in the motor with the kinetic energy of the load. The
load speed decreases; however, during kinetic buffering, the DC voltage remains constant.
After the line supply returns, the inverter immediately resumes normal operation.
Figure 6-40
262
Principle mode of operation of kinetic buffering
control). The V
DC min
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
control
DC min

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics g120p

Table of Contents