Advanced commissioning
8.19 Motor control
8.19.2.3

Advanced settings

K
- and T
adaptation
P
I
K
and T
p
measurement" of the motor data identification optimizes the speed controller. If you have
performed the rotating measurement, then the K
Additional information is provided in the List Manual:
• Vector control with speed controller: Function diagram 6050
• Vector control after presetting the application class Dynamic Drive Control: Function diagram
6824
Function description
For mechanically coupled drives, there is the risk that the drives oppose one another: Small
deviations in the speed setpoint or actual value of the coupled drives can mean that the drives
are operated with significantly different torques.
The droop function ensures even torque distribution between several mechanically coupled
drives.
The droop function reduces the speed setpoint as a function of the torque setpoint.
Figure 8-55
Parameter
Parameter
r1482
p1488[D]
p1489[D]
r1490
p1492[C]
When droop is active, the ramp-function generators of all of the coupled drives must be set to
have identical ramp-up and ramp-down times as well as rounding-off.
After selecting application class "Dynamic Drive Control", droop is no longer possible.
Additional information is provided in the List Manual, function diagram 6030.
300
adaptation suppress speed control oscillations that may occur. The "rotating
I
Effect of droop in the speed controller
Description
CO: Speed controller I torque output
Droop input source
Droop feedback scaling
CO: Droop feedback speed reduction
BI: Droop feedback enable
- and T
adaptation has been set.
p
n
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Factory setting
- Nm
0
0.05
- rpm
0