Electrical installation
4.11 Other connections
4.11.1
Clean Power version with integrated Line Harmonics Filter compact (Option
L01)
Description
Line Harmonics Filter compact reduce the converter's low-frequency line harmonic to a level
that complies with standard EN 61000-2-4, Class 2 and correspond to IEEE 519:1992.
Installation location, total width and total weight for Option L01
The Line Harmonics Filter compact is installed fully wired in an auxiliary cabinet. A 400 mm
or 600 mm wide cabinet is used depending on the unit rating and the voltage level. This
therefore increases the total width and the total weight of the cabinet.
Table 4- 30
6SL3710-1GE32-1AAx
6SL3710-1GE32-6AAx
6SL3710-1GE33-1AAx
6SL3710-1GE33-8AAx
6SL3710-1GE35-0AAx
6SL3710-1GE36-1AAx
6SL3710-1GE37-5AAx
6SL3710-1GE38-4AAx
6SL3710-1GE41-0AAx
6SL3710-2GE41-1AAx
6SL3710-2GE41-4AAx
6SL3710-2GE41-6AAx
116
Total width and total weight for Option L01
Order number
Unit rating of the
380 V -10 % ... 480 V +10 % 3 AC at 50 Hz
380 V -10 % ... 480 V +8 % 3 AC at 60 Hz
converter [kW]
Line voltage
110
132
160
200
250
315
400
450
560
630
710
900
Overall width
[mm]
1200
1200
1200
1400
1400
1800
1800
1800
2200
3600
3600
3600
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Total weight
[kg]
540
540
640
730
770
1300
1345
1555
1840
2580
2670
3090