9.5

Line filter

Dimensions for mounting the line filter
Table 9-3
Article number
6SL3203-0BE17-7BA0
6SL3203-0BE21-8BA0
6SL3203-0BE23-8BA0
Line filters are designed to IP20 degree of protection.
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
Technical data of the line filter (Class B)
Power
loss [W]
13
22
50
Connection
Line supply and Power
Module
2.5 mm
/ 0.8 Nm
2
14 AWG / 7 lbf in
6 mm
/ 1.8 Nm
2
10 AWG / 15.9 lbf in
16 mm
/ 4 Nm
2
6 AWG / 35.4 lbf in
Accessories
9.5 Line filter
PE
2.5 mm
/ 2 Nm
2
14 AWG / 17.7 lbf in
2.5 mm
/ 2 Nm
2
14 AWG / 17.7 lbf in
16 mm
/ 32 Nm
2
6 AWG / 26.5 lbf in
Weight
[kg]
1.75
4.0
7.3
129