Appendix D
Alternate Installation Procedures
Figure D-4
Step 14
If you use redundant power leads, repeat Steps
Use the "PWR A" and "PWR B" labels provided with the MIC to designate the power leads.
Step 15
Caution
In case a power cable is damaged or cut, Cisco recommends that you diversely route redundant power
leads along different paths. If you installed the tie-down bar, you can run one power lead across the
tie-down bar and secure it using tie-wraps or other site-specific methods. You should route the other
power cable in the opposite direction.
Figure D-5
March 2003
NTP-B222 Connect Office Power to the ONS 15327 Shelf (Terminal-Lug Power Connector)
Power Cable Inserted into the MIC Terminal-Lug Power Connector
shows redundant power connected to an ONS 15327.
5
through
12
for the other MIC.
Cisco ONS 15327 Procedure Guide, R4.0
D-7