Download Print this page

Secure The Power Cord On The Power Supply Module - Cisco Firepower 2130 Installation & Maintenance

Hide thumbs Also See for Firepower 2130:

Advertisement

Secure the Power Cord on the Power Supply Module

Figure 6: Tighten the Terminal Block Captive Screws
Negative (-) lead wire
1
Step 6
Repeat these steps for the remaining DC input power source wire as applicable.
Step 7
Use a tie wrap to secure the wires to the rack, so that the wires are not pulled from the terminal block.
Step 8
Set the DC disconnect switch in the circuit to ON. In a system with multiple power supplies, connect each power supply
to a separate DC power source. In the event of a power source failure, if the second source is still available, it can maintain
system operation.
Step 9
Verify power supply operation by checking the power supply LED on the front of the chassis. See
the LED values.
Secure the Power Cord on the Power Supply Module
To secure the power supply module against accidental removal and thus prevent disrupting system performance,
use the tie wrap and clamp provided in the accessories kit that ships with your Firepower 2100.
Safety Warnings
Installation, Maintenance, and Upgrade
14
Take note of the following component replacement safety warnings:
Installation, Maintenance, and Upgrade
Positive (+) lead wire
2
Front Panel LEDs
for

Advertisement

loading

This manual is also suitable for:

Firepower 2140