SINUMERIK 808D ADVANCED alarms
3.2 NCK alarms
Remedy:
H numbers must be assigned only once in a TO unit. Then, MD10890, $MN_EXTERN_TOOLPROG_MODE, bit 3 can
be set = 0 and a restart can be performed.
Program
Clear alarm with the Delete key or NC START.
Continuation:
4600
Invalid handwheel type for handwheel %1
Parameters:
%1 = Handwheel number
Definitions:
The handwheel type (hardware segment) for handwheel %1 requested through MD11350
$MN_HANDWHEEL_SEGMENT is invalid.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Configure a valid type for the corresponding handwheel through MD11350 $MN_HANDWHEEL_SEGMENT.
Program
Switch control OFF - ON.
Continuation:
4610
Invalid handwheel module for handwheel %1
Parameters:
%1 = Handwheel module
Definitions:
For SINUMERIK 840D and SINUMERIK 840DI only:
The handwheel module for handwheel %1 requested through MD11351 $MN_HANDWHEEL_MODULE is not
available for 840D systems. An 840D system is always regarded as a module. Therefore MD11351
$MN_HANDWHEEL_MODULE = 1 must always be set for handwheels directly linked to 840D systems.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Set machine date MD11351 $MN_HANDWHEEL_MODULE = 1 for the corresponding handwheel.
Program
Switch control OFF - ON.
Continuation:
4611
Invalid handwheel input for handwheel %1
Parameters:
%1 = Handwheel input
Definitions:
For SINUMERIK 840D and SINUMERIK 840Di only:
The handwheel input for handwheel %1 requested through MD11352 $MN_HANDWHEEL_INPUT is not available for
840D systems. A maximum of 2 or 3 handwheels can be linked directly to 8xxD systems.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Configure MD11352 $MN_HANDWHEEL_INPUT for a valid input for the corresponding handwheel
Program
Switch control OFF - ON.
Continuation:
4620
Invalid handwheel module for handwheel %1
Parameters:
%1 = Handwheel module
Definitions:
The handwheel module for handwheel %1 requested through MD11351 $MN_HANDWHEEL_MODULE is not
available for 802D sl, 828D sl, 808D systems. 802D sl, 828D sl, 808D systems are always regarded as modules.
Therefore MD11351 $MN_HANDWHEEL_MODULE = 1 must always be set for directly linked handwheels.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Set machine data MD11351 $MN_HANDWHEEL_MODULE = 1 for the corresponding handwheel.
For 840D sl systems, MD11350 $MN_HANDWHEEL_SEGMENT should be checked.
Program
Switch control OFF - ON.
Continuation:
4621
Invalid handwheel input for handwheel %1
Parameters:
%1 = Handwheel input
80
Diagnostics Manual, 08/2013, 6FC5398-6DP10-0BA1