Program
Clear alarm with the RESET key. Restart part program
Continuation:
15810
[Channel %1: ] Block %2 wrong array dimension for CONTPRON/CONTDCON
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
The number of columns for the array created for CONTPRON/CONTDCON does not conform to the current
programming guide.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Modify part program.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
15900
[Channel %1: ] Block %2 touch probe not allowed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Measure with deletion of distance-to-go
In the part program, an illegal probe has been programmed with the command MEAS (measure with deletion of
distance-to-go). The probe numbers
0 ... no probe
1 ... probe 1
2 ... probe 2
are allowed, whether the probe is actually connected or not.
Example:
N10 MEAS=2 G01 X100 Y200 Z300 F1000
Probe 2 with deletion of distance-to-go
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Include a probe number within the limits given above in the keyword MEAS=... This must correspond to the hardware
connection of the probe.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
15910
[Channel %1: ] Block %2 touch probe not allowed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Measure without deletion of distance-to-go
In the part program, an illegal probe has been programmed with the command MEAW (measure without distance-to-
go). The probe numbers
0 ... no probe
1 ... probe 1
2 ... probe 2
are allowed, whether the probe is actually connected or not.
Example:
N10 MEAW=2 G01 X100 Y200 Z300 F1000
Probe 2 without deletion of distance-to-go
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Include a probe number within the limits given above in the keyword MEAW=... This must correspond to the hardware
connection of the probe.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
Diagnostics Manual
Diagnostics Manual, 08/2013, 6FC5398-6DP10-0BA1
SINUMERIK 808D ADVANCED alarms
3.2 NCK alarms
223