SINUMERIK 808D ADVANCED alarms
3.5 Cycle alarms
61420
[Channel %1: ] Block %2: Check calibration of multi/mono probes.
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Remedy:
The workpiece probe must be calibrated according to its type and use.
61421
[Channel %1: ] Block %2: Software release of measuring cycles or NCK inadequate or
set up incorrectly - error code %4
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Remedy:
Causes of error:
1. Error code = A
61422
[channel %1: ] block %2: parameter measuring variant incorrect - error code: %4
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Remedy:
1. Error code = A
Error code = A
2. Error code = B
Error code = B
3. Error code = C -> Measurement version "compute kinematics" active, but rotary axes 1 and/or 2 not measured
(see also parameter _OVR[40])
4. Error code = D -> (_MVAR dec5) - _MVAR TEN THOUSANDS digit (parameter rotary axis 1, 2 or vector chain
open, closed) outside the value range 0..3
61423
[Channel %1: ] Block %2: Parameter %4 not agreed or not created
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Remedy:
Causes of error:
For 840D sl - up to SW 2.6 SP1 and for 828D - up to SW 4.3:
1. Parameter CYCLE996 _TNUM incorrect or equals zero
2. No swivel data record created -> MD18088 = 0
For 840D sl - as from SW 2.7 and for 828D - as from SW 4.4:
1. Parameter CYCLE996 S_TC incorrect or equals zero
2. No swivel data record created -> MD18088 = 0
61424
[Channel %1: ] Block %2: Parameter %4 for diameter of calibration ball incorrect
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Remedy:
Check whether the correct diameter of the calibration ball is entered in parameter S_SETV,
or the correct probe ball radius is entered in the tool data of the current workpiece probe.
The mechanical deviation of the position of the current workpiece probe must be minimized by presetting.
398
->
_OVR[] - parameter field too small. Check GUD definition.
DEF CHAN REAL _OVR[72] (up to MZ06.03.xx.xx =32)
->
_MVAR = 9x identifiers CYCLE996 measure kinematics or
->
_MVAR ONES digit outside the value range 0..4
->
_MVAR (parameter for normalization) HUNDRED THOUSANDS digit (dec6) or
-> ONE MILLION digit (dec7) outside the value range 0..3
or rotary axis 2 exists and no rotary axis vectors (V2xyz) are set up.
Diagnostics Manual, 08/2013, 6FC5398-6DP10-0BA1