SINUMERIK 808D ADVANCED alarms
3.2 NCK alarms
16932
[Channel %1: ] Conflict when activating user data type %2
Parameters:
%1 = Channel number
%2 = Data type
Definitions:
The "activate user data" function (PI service _N_SETUDT) modifies a data block (tool offset, settable work offset or
base frame) which is also written by the NC blocks in preparation.
In the event of a conflict, the value entered by the HMI is reset.
Parameter %2 specifies which data block is affected:
1: Active tool offset
2: Base frame
3: Active work offset
Reaction:
Alarm display.
Remedy:
Check the inputs on the HMI and repeat if necessary.
Program
Clear alarm with the Delete key or NC START.
Continuation:
16933
[Channel %1: ] Interrupt treatment: action %2<ALNX> not allowed in the current state
Parameters:
%1 = Channel number
%2 = Action number/action name
Definitions:
If a temporary standstill has occurred because of a Reorg event across block boundaries, it is possible that a block
without Reorg capability has been loaded. In this situation, it is unfortunately necessary to cancel the Reorg event
handling! Reorg events are, e.g. cancelation subprogram, delete distance-to-go and interrupts.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Cancel program with the RESET key.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
16934
[Channel %1: ] Interrupt treatment: action %2<ALNX> not possible due to stop
Parameters:
%1 = Channel number
%2 = Action number/action name
Definitions:
Reorg events are, e.g. cancelation subprogram, delete distance to go and interrupts, axis exchange, termination of
follow-up mode. Two Reorg events overlap in this situation. The 2nd Reorg event coincides with the 1st block
generated by the previous event. (e.g. an axis exchange is induced twice in rapid succession). Axis exchange leads
to Reorg in the channels in which an axis is removed without preparation. This block must be stopped in the above
sequence in order to prevent the interpolator buffer from overflowing. This can be achieved by pressing the Stop or
StopAll key, configuring an alarm with INTERPRETERSTOP or by decode single block.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
The program must be canceled with Reset.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
16935
[Channel %1: ] Action %2<ALNX> not possible due to search run
Parameters:
%1 = Channel number
%2 = Action number/action name
Definitions:
The action is not allowed as block search is currently running via program test. Block search via program test: "PI
Service _N_FINDBL with mode parameter 5.
With this block search type, it is not permissible to activate program test or dry run feedrate.
Reaction:
Alarm display.
Remedy:
Activate the action after block search is terminated.
244
Diagnostics Manual, 08/2013, 6FC5398-6DP10-0BA1