In Pr.06-08 to Pr.06-11 the four most recent faults that occurred, are stored. After removing the cause of
the fault, use the reset command to reset the drive.
06 - 12

Under-Current Detection Level

Settings
06 - 13
Under-Current Detection Time
Settings

Under-Current Detection Mode

06 - 14
Settings
06 - 15

Under-Current Detection Restart Delay Time

Settings
If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting during operation,
the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC drive will restart after the delay
time set by Pr.06-15 is up.
06 - 16
User-Defined Low-Voltage Detection Level (Lv)
Settings
06 - 17
User-Defined Low-Voltage Detection Time
Settings
Revision 10/2005, BE13, SW V4.08
00 ~ 100%
00 Disabled
0.1~ 3600.0 sec
00
Warn and keep operating
01
Warn and ramp to stop
02
Warn and coast to stop
03
Warn, after coast to stop, restart (delay 06-15 setting time)
1~600 min
00 Disabled
230V series: 220 ~ 300VDC
460V series: 440 ~ 600VDC
575V series: 520 ~ 780VDC
0.1~ 3600.0 sec
Chapter 5 Parameters VFD-B Series
Factory Setting: 00
Factory Setting: 10.0
Factory Setting: 00
Factory Setting: 10
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 0.5
Unit: 1
Unit: 0.1
Unit: 1
Unit: 1
Unit: 0.1
5-77