Mounting; Mounting Sequence - WAGO I/O-SYSTEM 750 XTR Manual

2di 220v dc 3.0ms/xtr 2-channel digital input module 220 vdc, 2- to 4-wire connection, high-side switching/xtr
Hide thumbs Also See for I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

30

Mounting

Pos : 53 /All e Seri en (Allgemei ne Module)/Ü berschriften/N eue Ü berschriften/Ebene 1M ontier en - Übersc hrift 1 @ 3\mod_1225446744750_21.doc x @ 24900 @ 1 @ 1
5
Mounting
Pos : 54.1 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/M ontagerei henfolge @ 3\mod_1231770210031_21.doc x @ 25992 @ 2 @ 1
5.1

Mounting Sequence

Fieldbus couplers/controllers and I/O modules of the WAGO-I/O-SYSTEM
750/753 are snapped directly on a carrier rail in accordance with the European
standard EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler/controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos : 54.2 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Vorsic ht/Vorsicht: Verl etz ungsgefahr durc h s charfkantige M ess er kontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
Pos : 54.3 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Achtung/Achtung: Bus kl emmen nur in vorgesehener R eihenfolg e stec ken! @ 6\mod_1256194177073_21.doc x @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the top.
This mechanical coding helps to avoid configuration errors, which may destroy
the I/O modules. Therefore, insert I/O modules only from the right and from the
top.
Pos : 54.4 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Hinweis/Hi nweis: Busabsc hluss XTR nicht vergess en! @ 15\mod_1368426836647_21.doc x @ 119458 @ @ 1
Don't forget the bus end module!
Always plug a bus end module 750-600/040-000 onto the end of the fieldbus
node! You must always use this bus end module at all fieldbus nodes with the
WAGO I/O System 750 XTR fieldbus couplers/controllers to guarantee proper
data transfer.
Pos : 54.5 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/Bus klemmen 750xxxx/0040xxxx 4g-5g @ 15\mod_1367558844291_21.doc x @ 118470 @ @ 1
For vibration loads > 4g, observe the following installation instructions:
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
Make the open conductor length between strain relief and wire connection
as short as possible.
Use the reinforced end stop 249-197.
Pos : 54.6 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms /XTR
Manual
Version 1.2.0

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-407/040-000

Table of Contents