Settings Options; Module Parameters; Table 33 Module Parameters - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

765-1205/100-000

6.3 Settings Options

6.3.1 Module Parameters

Indexes 0x2000 to 0x2003
Parameters with indexes 0x2000 to 0x2003 configure the module.
Index
Subindex
0x2000.0
0
0x2001.0
0
0x2002.0
1
0x2002.0
2
0x2003.0
1
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Value Range
Value Range
Force mode setting
0: Force mode en-
able
1: Force mode dis-
able
PD layout configura-
0: port-based
tion
1: pin-based
DO substitue mode
0: Set to low
1: Use substitute val-
ues
2: hold last
DO substitue value
0 ... 65535
Disable BT
0: Activation of BT in-
terface is allowed
1: Disable activation
of BT interface
Table 33: Module Parameters
Default
Description
0
The "Forcing" operating mode may be
used.
The "Forcing" operating mode must not be
used.
0
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4, bit 1 = port X01
pin 2,
bit 2 = port X02 pin 4, bit 3 = port X02
pin 2, ...
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4, Bit 1 = port X02
pin 4,
bit 2 = port X03 pin 4, bit 3 = port X04 pin 4,
...
bit 8 = port X01 pin 2, bit 9 = port X02
pin 2, ...
0
Set all digital outputs to low level in the
event of error
Set digital outputs to a pre-defined substi-
tute value in the event of error.
If this setting is used, the value of the "DO
substitute value" parameter determines the
substitute value.
Hold digital outputs at their last value in the
event of error
0
Substitute value for the digital outputs if the
"Use substitute values" setting is used. The
input depends on the "PD layout configura-
tion" parameter.
Use a binary-to-decimal converter to calcu-
late this value.
®
0
The Bluetooth
interface can be enabled by
an optical signal of a mobile device and in
connection with the WAGO I/O Field app.
®
The Bluetooth
interface cannot be enabled
by an optical signal of a mobile device and
in connection with the WAGO I/O Field app.
Planning
41