Programming Guide | VLT® AutomationDrive FC 360
3-50 Ramp 2 Type
Default value:
[0] Linear
Setup:
All setups
Data type:
Uint8
Select the ramp type, depending on requirements for acceleration/deceleration. A linear ramp gives constant acceleration during
ramping. A sine 2 ramp gives non-linear acceleration.
Option
[0]
[2]
3-51 Ramp 2 Ramp Up Time
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Enter the ramp-up time, which is the acceleration time from 0 Hz to the rated motor speed n
output current does not exceed the current limit in parameter 4-18 Current Limit during ramping. See ramp-down time in parameter
3-52 Ramp 2 Ramp Down Time.
3-52 Ramp 2 Ramp Down Time
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Enter the ramp-down time, which is the deceleration time from the rated motor speed n
Nm if the torque configuration modes are selected. Select a ramp-down time such that no overvoltage arises in the inverter due to
regenerative operation of the motor, and such that the generated current does not exceed the current limit set in parameter 4-18
Current Limit. See ramp-up time in parameter 3-51 Ramp 2 Ramp Up Time.
3-6* Ramp 3
4.4.5
This parameter group configures ramp 3 parameters.
3-60 Ramp 3 Type
Default value:
[0] Linear
94
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Name
Linear
Sine 2 Ramp
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Option
–
True
Description
Linear ramp.
Sine 2 ramp based on the values set in
parameter 3-51 Ramp 2 Ramp Up Time
and parameter 3-52 Ramp 2 Ramp Down
Time.
Range (0.01–3600.00 s)
-2
True
. Select a ramp-up time such that the
S
Range (0.01–3600.00 s)
-2
True
to 0 Hz or from the nominal torque to 0
s
Option
AU275649936274en-001401 / 130R0507