Programming Guide | VLT® AutomationDrive FC 360
Data type:
Int32
Use this parameter to set a low limit for the feedback range. When the feedback drops below this limit, the display shows Feedb Low. Bit
6 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP
warning indicator light is not turned on when this parameter set limit is reached.
4-57 Warning Feedback High
Default value:
4999.000 ProcessCtrlUnit
Setup:
All setups
Data type:
Int32
Use this parameter to set a high limit for the feedback range. When the feedback exceeds this limit, the display reads Feedb High. Bit 5
is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP
warning indicator light is not turned on when this parameter set limit is reached.
4-58 Missing Motor Phase Function
Default value:
[1] Trip 10s
Setup:
All setups
Data type:
Uint8
Turn on the missing motor phase function or trip.
Option
[0]
[1]
[6]
4-59 Motor Check At Start
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
3-phase motor check at start.
Option
[0]
[1]
Danfoss A/S © 2024.01
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Off
Trip 10s
Trip 1s 3ph detec.
Parameter type:
Conversion index:
Change during operation:
Name
Off
On
AU275649936274en-001401 / 130R0507 |
True
Range (-4999.000–4999.000
ProcessCtrlUnit)
-3
True
Option
–
False
Option
–
True
107
Need help?
Do you have a question about the VLT AutomationDrive FC 360 and is the answer not in the manual?
Questions and answers