Danfoss VLT AutomationDrive FC 360 Programming Manual page 125

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Programming Guide | VLT® AutomationDrive FC 360
Option
[81]
[82]
[83]
[91]
[95]
[160]
[161]
[165]
[166]
[167]
[168]
[169]
[170]
Danfoss A/S © 2024.01
Name
SL digital output B
SL digital output C
SL digital output D
Encoder emulate output A
Power Loss Detection
No alarm
Running reverse
Local ref active
Remote ref active
Start command active
Drive in hand mode
Drive in auto mode
Homing Completed
Description
See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [39] Set dig. out. B high is
executed. The output goes low whenever
the Smart Logic Action [33] Set dig. out. B
low is executed.
See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [40] Set dig. out. C high is
executed. The output goes low whenever
the Smart Logic Action [34] Set dig. out. C
low is executed.
See parameter 13-52 SL Controller Action.
The output goes high whenever the Smart
Logic Action [41] Set dig. out. D high is
executed. The output goes low whenever
the Smart Logic Action [35] Set dig. out. D
low is executed.
The output is high when no alarm is
present.
The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
The output is high when the drive is
running counterclockwise (the logical
product of the status bits Running AND
Reverse).
The output is high when the drive is in
hand-on mode.
The output is high when the drive is in
auto-on mode.
The homing operation is completed. This
option is only effective when parameter
37-00 Application Mode is set to [2]
Position Control.
AU275649936274en-001401 / 130R0507 |