Programming Guide | VLT® AutomationDrive FC 360
Option
[0]
[1]
[2]
2-19 Over-voltage Gain
Default value:
100%
Setup:
All setups
Data type:
Uint16
This parameter enables the user to fine-tune the Over-voltage gain for parameter 2-17 Over-voltage Control. It is not necessary to
change this parameter for normal applications.
2-2* Mechanical Brake
4.3.3
2-20 Release Brake Current
Default value:
0.00 A
Setup:
All setups
Data type:
Uint32
Set the motor current for release of the mechanical brake when a start condition is present.
When mechanical brake control output is selected, but no mechanical brake is connected, the function does not work by default
setting due to too low motor current.
2-22 Activate Brake Speed [Hz]
Default value:
0.0 Hz
Setup:
All setups
Data type:
Uint16
82
| Danfoss A/S © 2024.01
Name
Disabled
Enabled (not at stop)
Enabled
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
  NOTICE
Parameter type:
Conversion index:
Change during operation:
Description
No OVC required.
Activate OVC except when using a stop
signal to stop the drive.
Activate OVC.
  CAUTION
PERSONAL INJURY AND
EQUIPMENT DAMAGE
Enabling OVC in hoisting
applications may lead to personal
injuries and equipment damage.
DO NOT enable OVC in
l
hoisting applications.
Range (0–1000%)
0
True
Range (0.00–100.00 A)
-2
True
Range (0.0–400.0 Hz)
-1
True
AU275649936274en-001401 / 130R0507