Programming Guide | VLT® AutomationDrive FC 360
Data type:
Uint16
Specify the maximum allowed delay time between receiving a request and sending the response. If this time is exceeded, no response is
returned.
8-4* FC MC protocol set
4.9.4
8-42 PCD Write Configuration
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Select the parameters to be assigned to the PCD's telegrams. The number of available PCDs depends on the telegram type. The values in
the PCDs are then written to the selected parameters as data values.
Enter up to 16 different preset mapping 0–15 in this parameter, using array programming. If this parameter is active, addresses 2810–
2825 represent values of the 16 parameters. If this parameter is not active, addresses 2810 and 2811 are used as input-data-drive control
word and bus reference. Addresses 2812–2825 are reserved.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[15]
[16]
[18]
[19]
[20]
176
| Danfoss A/S © 2024.01
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
None
[302] Minimum Reference
[303] Maximum Reference
[341] Ramp 1 Ramp up time
[342] Ramp 1 Ramp down time
[351] Ramp 2 Ramp up time
[352] Ramp 2 Ramp down time
[380] Jog Ramp Time
[381] Quick Stop Time
[412] Motor Speed Low Limit [Hz]
[414] Motor Speed High Limit [Hz]
[590] Digital & Relay Bus Control
[676] Terminal 45 Output Bus Control
[696] Terminal 42 Output Bus Control
FC Port CTW
FC Port REF
[311] Jog Speed [Hz]
[427] Torque limit bus control
[428] Speed limit bus control
True
Option, Array [16]
True