Programming Guide | VLT® AutomationDrive FC 360
5-56 Term. 33 High Frequency
Default value:
32000 Hz
Setup:
All setups
Data type:
Uint32
Enter the high frequency corresponding to the high motor shaft speed (that is high reference value) in parameter 5-58 Term. 33 High
Ref./Feedb. Value.
5-57 Term. 33 Low Ref./Feedb. Value
Default value:
0.000
Setup:
All setups
Data type:
Int32
Enter the low reference value [Hz] for the motor shaft speed. This value is also the low feedback value. See also parameter 5-52 Term. 29
Low Ref./Feedb. Value.
5-58 Term. 33 High Ref./Feedb. Value
Default value:
Size related
Setup:
All setups
Data type:
Int32
Enter the high reference value [Hz] for the motor shaft speed. See also parameter 5-53 Term. 29 High Ref./ Feedb. Value.
5-59 Term.33 Pulse Filter Time Constant
Default value:
100 ms
Setup:
All setups
Data type:
Uint16
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal, an advantage when there is a lot of
noise. A high value results in better dampening but also increases the time delay through the filter.
5-6* Pulse Output
4.6.6
Use these parameters to configure pulse outputs with their functions and scaling. Terminal 27 and 29 are allocated to pulse output via
parameter 5-01 Terminal 27 Mode and parameter 5-02 Terminal 29 Mode.
138
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Range (5–32000 Hz)
–
True
Range (-4999.000–4999.000)
-3
True
Range (-4999.000–4999.000)
-3
True
Range (1–1000 ms)
-3
False
AU275649936274en-001401 / 130R0507