Programming Guide | VLT® AutomationDrive FC 360
21-18 Ext. 1 Feedback [Unit]
Default value:
0.000 ExtPID1Unit
Setup:
All setups
Data type:
Int32
Return the feedback value.
21-19 Ext. 1 Output [%]
Default value:
0%
Setup:
All setups
Data type:
Int32
Return the extended closed loop 1 PID controller output value.
21-2* Ext. CL 1 PID
4.18.3
21-20 Ext. 1 Normal/Inverse Control
Default value:
[0] Normal
Setup:
All setups
Data type:
Uint8
Select the normal or inverse control.
Option
[0]
[1]
21-21 Ext. 1 Proportional Gain
Default value:
0.01
Setup:
All setups
Data type:
Uint16
The proportional gain indicates the number of times the error between the setpoint and the feedback signal is to be applied.
21-22 Ext. 1 Integral Time
Default value:
10000.00 s
Setup:
All setups
Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Normal
Inverse
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Range (-999999.999–
999999.999 ExtPID1Unit)
-3
True
Range (0–100%)
0
True
Option
True
Description
Select [0] Normal if the controller output
should be reduced when the feedback is
higher than the reference.
Select [1] Inverse if the output should be
increased when the feedback is higher
than the reference.
Range (0.00–10.00)
-2
True
Range (0.01–10000.00 s)
-2
AU275649936274en-001401 / 130R0507 |