Programming Guide | VLT® AutomationDrive FC 360
Option
[0]
[1]
[2]
8-03 Control Timeout Time
Default value:
1.0 s
Setup:
1 setup
Data type:
Uint16
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates that
the serial communication has stopped. The function that is selected in parameter 8-04 Control Timeout Function is then carried out.
8-04 Control Timeout Function
Default value:
[0] Off
Setup:
1 setup
Data type:
Uint8
Select the timeout function. The timeout function activates when the control word fails to be updated within the time period specified in
parameter 8-03 Control Word Timeout Time.
Option
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[26]
172
| Danfoss A/S © 2024.01
Name
None
FC Port
Option A
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
Qstop and trip
Trip
Description
PROFIBUS and PROFINET.
Range (0.1 s–6000.0 s)
-1
True
Option
–
True
Description
Resume control via fieldbus (fieldbus or
standard), using the most recent control
word.
Freeze output frequency until
communication resumes.
Stop with auto restart until
communication resumes.
Run the motor at jog frequency until
communication resumes.
Run the motor at maximum frequency
until communication resumes.
Stop the motor and trip, then reset the
drive to restart:
• Via fieldbus.
• Via [Reset].
• Via a digital input.
AU275649936274en-001401 / 130R0507