Starting and stopping the SLC
Start and stop the SLC by selecting [1] On or [0] Off in parameter 13-00 SL Controller Mode. The SLC always starts in state 0 (where it
evaluates event [0]). The SLC starts when the Start Event (defined in parameter 13-01 Start Event) is evaluated as true (if [1] On is selected
in parameter 13-00 SL Controller Mode). The SLC stops when the stop event (parameter 13-02 Stop Event) is true. Parameter 13-03 Reset
SLC resets all SLC parameters and starts programming from scratch.
SLC is only active in auto-on mode, not hand-on mode.
13-0* SLC Settings
4.12.2
Use the SLC settings to activate, deactivate, and reset the smart logic control sequence. The logic functions and comparators are always
running in the background, which opens for separate control of digital inputs and outputs.
13-00 SL Controller Mode
Default value:
[0] Off
Setup:
1 setup
Data type:
Uint8
Enable or disable the smart logic controller.
Option
[0]
[1]
13-01 Start Event
Default value:
[39] Start command
Setup:
1 setup
Data type:
Uint8
Select the condition (TRUE or FALSE) which activates the Smart Logic Controller.
Option
[0]
[1]
[2]
[3]
[4]
[7]
[8]
212
| Danfoss A/S © 2024.01
  NOTICE
Parameter type:
Conversion index:
Change during operation:
Name
Off
On
Parameter type:
Conversion index:
Change during operation:
Name
False
True
Running
In range
On reference
Out of current range
Below I low
Option
True
Option
True