Programming Guide | VLT® AutomationDrive FC 360
35-2* Temp. Input X48/7
4.24.4
35-24 Term. X48/7 Filter Time Constant
Default value:
0.005 s
Setup:
All setups
Data type:
Uint16
Enter the filter time constant. This is a first-order digital lowpass filter time constant for suppressing electrical noise in terminal X48/7. A
high time constant value improves dampening but also increases the time delay through the filter.
35-25 Term. X48/7 Temp. Monitor
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/7. The temperature limits can be
set in parameter 35-26 Term. X48/7 Low Temp. Limit/parameter 35-27 Term. X48/7 High Temp. Limit.
Option
[0]
[1]
35-26 Term. X48/7 Low Temp. Limit
Default value:
-50
Setup:
All setups
Data type:
Int16
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
35-27 Term. X48/7 High Temp. Limit
Default value:
204
Setup:
All setups
Data type:
Int16
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
35-3* Temp. Input X48/10
4.24.5
35-34 Term. X48/10 Filter Time Constant
Default value:
0.005 s
Setup:
All setups
Data type:
Uint16
296
| Danfoss A/S © 2024.01
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Name
Disabled
Enabled
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Range (0.005–10.000 s)
-3
True
Option
True
Range (-50–204)
0
True
Range (-50–204)
0
True
Range (0.005–10.000 s)
-3
True
AU275649936274en-001401 / 130R0507