Programming Guide | VLT® AutomationDrive FC 360
Option
[1]
[2]
[9]
0-11 Programming Set-up
Default value:
[9] Active Set-up
Setup:
1 setup
Data type:
Uint8
Select the setup to be programmed during operation, either the active setup or the inactive setup. The setup number being edited
flashes in the LCP.
Option
[1]
[2]
[9]
0-12 Link Setups
Default value:
[20] Linked
Setup:
All setups
Data type:
Uint8
The link ensures synchronizing of the Not changeable during operation parameter values enabling shift from 1 setup to another during
operation. If the setups are not linked, a change between them is not possible while the motor is running. Thus the setup change does
not occur until the motor is coasted.
Option
[0]
[20]
36
| Danfoss A/S © 2024.01
Name
Set-up 1
Set-up 2
Multi Set-up
Parameter type:
Conversion index:
Change during operation:
Name
Set-up 1
Set-up 2
Active Set-up
Parameter type:
Conversion index:
Change during operation:
Name
Not linked
Linked
Description
Setup 1 is active.
Setup 2 is active.
This option is used for remote setup
selections via digital inputs and the serial
communication port. This setup uses the
settings from parameter 0-12 Link Setups.
Option
–
True
Description
Setup 1 can be edited freely during
operation, independently of the active
setup.
Setup 2 can be edited freely during
operation, independently of the active
setup.
The setup in which the drive is operating
can also be edited during operation.
Option
–
False
Description
Leave parameters unchanged in both
setups. These parameters cannot be
changed while the motor is running.
Copy Not changeable during operation
parameters from 1 setup to the other, so
they are identical in both setups.
AU275649936274en-001401 / 130R0507