Programming Guide | VLT® AutomationDrive FC 360
Select [0] Disabled to avoid accidental stop or reset of the drive from LCP. Setting can be locked by parameter 0-60 Main Menu Password.
Option
[0]
[1]
[7]
0-5* Copy/Save
4.1.7
0-50 LCP Copy
Default value:
[0] No copy
Setup:
1 setup
Data type:
Uint8
Copy parameters from and to the LCP.
Option
[0]
[1]
[2]
[3]
0-51 Set-up Copy
Default value:
[0] No copy
Setup:
1 setup
Data type:
Uint8
Copy parameters between factory settings and the parameter setups.
Option
[0]
[1]
Danfoss A/S © 2024.01
Name
Disabled
Enabled
Enable Reset Only
Parameter type:
Conversion index:
Change during operation:
Name
No copy
All to LCP
All from LCP
Size indep. from LCP
Parameter type:
Conversion index:
Change during operation:
Name
No copy
Copy from setup 1
Description
Avoid accidental stop or reset of the drive
from LCP.
[Off/Reset] mode is enabled.
Only Reset is enabled.
Option
False
Description
No function.
Copy all parameters in all set-ups from
the drive memory to the LCP. For service
purposes, copy all parameters to the LCP
after commissioning.
Copy all parameters in all set-ups from the
LCP memory to the drive memory.
Copy only the parameters that are
independent of the motor size. This
selection can be used to program several
drives with the same function without
disturbing motor data that is already set.
Option
False
Description
No function.
Copy from setup 1 to setup 2.
AU275649936274en-001401 / 130R0507 |
47